Function library

Limit value setting
Current limits

10

l

284

EDS82EV903 EN 3.0

10.5.2

Current limits

Description

The controllers are equipped with a current−limit control which determines the dynamic
response under load. The measured load is compared with the limit values set under C0022
for motor load and C0023 for generator load. If the current limit is exceeded, the controller
will change its dynamic behaviour:

Controller performance when a limit value is reached

Motor overload during acceleration:

The controller prolongs the acceleration ramp.

Generator overload during deceleration:

The controller prolongs the deceleration ramp.

With increasing load and constant speed:

ƒ

When the current limit of the motor mode is reached:
– The controller reduces the output frequency to 0 Hz.
– The controller cancels the change of the output frequency if the load falls below

the limit value.

ƒ

When the current limit in the generator mode is reached:
– The controller increases the output frequency up to the maximum frequency

(C0011).

– The controller cancels the change of the output frequency if the load falls below

the limit value.

ƒ

If suddenly a load is applied to the motor shaft (e.g. drive is blocked), the overcurrent
switch−off can be activated (error message OCX).

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0022 I

max

limit in

motor mode

150

30

{1 %}

150 Only 8200 vector 15 ... 90 kW):

If C0022 = 150 %, 180 % I

rated

are

available for max. 3 s after
controller enable.

^ 284

C0023 I

max

limit in

generator
mode

150

30

{1 %}

150 C0023 = 30 %: function inactive if

C0014 = 2, 3

^ 284

Adjustment

ƒ

Set the acceleration and deceleration times so that the drive can follow the speed
profile without reaching I

max

of the controller.

ƒ

C0022 and C0023 refer to the rated output current at a switching frequency of 8
kHz.

ƒ

When operating with a switching frequency of 16 kHz you must adapt C0022 and
C0023 to the permissible output currents (derating).

ƒ

Correct current control for operation in generator mode is only possible with
external brake resistor.