10 safety function - connection of relay ksr, Safety function − connection of relay ksr, Extensions for automation – Lenze E82xVxxxKxxxxx User Manual
Page 189: External voltage supply, 10 safety function − connection of relay k
Extensions for automation
Standard devices in a power range from 15 ... 90 kW
Wiring of controller inhibit (CINH) when two function modules are operated
l
189
EDS82EV903 EN 3.0
7.3.9
Wiring of controller inhibit (CINH) when two function modules are operated
)
Note!
ƒ
Both terminals X3/28 of the interface FIF I and FIF II are evaluated internally
via an AND−operation.
ƒ
The following illustrations show possible methods of wiring. Considering
the AND−operation of both terminals X3/28, wiring can be adapted to your
application.
Internal DC voltage supply
FIF I
39 7
+20V
28
20
X3
GND3
GND1
62
9
7 20 28 E1 E2 E3 E4 39 A1 59
E82ZAFSC010
E82ZAFx
FIF II
+20V
+5V
X3
GND1
GND2
0.5...0.6 Nm
4.4...5.3 lb-in
X3
PES
PES
0
8200vec262
Fig. 7−13
Wiring of the controller inhibit with internal voltage supply
0
For function modules with terminals X3/7 and X3/39: Install a wire jumper between X3/7
and X3/39
PES
HF shield termination by large−surface connection to PE
Wiring of the other terminals:
^ Mounting instructions of the function modules
External voltage supply
FIF I
39 7
+20V
28
20
X3
GND2
GND1
62
9
7 20 28 E1 E2
+
–
E3 E4 39 A1 59
E82ZAFSC010
E82ZAFx
FIF II
+20V
24 V ext.
(
+30 V +0 %, max. 120 mA)
+12 V -0 % ...
…
+5V
X3
GND1
GND2
0.5...0.6 Nm
4.4...5.3 lb-in
X3
PES
PES
0
8200vec263
Fig. 7−14
Wiring of the controller inhibit with external voltage supply
0
For function modules with terminals X3/7 and X3/39: Install a wire jumper between X3/7
and X3/39
PES
HF shield termination by large−surface connection to PE
Wiring of the other terminals:
^ Mounting instructions of the function modules
7.3.10
Safety function − connection of relay K
SR
)
Note!
A complete description of the "Safe torque off" function can be found in the
chapter "Safety system"(
¶ 492).