Function library, Code table – Lenze E82xVxxxKxxxxx User Manual

Page 392

Advertising
background image

Function library

Code table

10

l

392

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0111

v

Configuration
of analog
output X3/62
(AOUT1−IN)

Output of analog signals to terminal

Change of C0111 is copied into
C0419/1. Free configuration in
C0419/1 sets C0111 = −255−!

^ 332

0

0

Output frequency with slip
(MCTRL1−NOUT+SLIP)

6 V/12 mA

º C0011

1

Device utilisation (MCTRL1−MOUT) at
V/f characteristic control (C0014 = 2 or
3)

3 V/6 mA

º rated active inverter

current (active current/C0091)

Actual motor torque (MCTRL1−MACT)
with vector control (C0014 = 4) or
sensorless torque control (C0014 = 5)

3 V/6 mA

º rated motor torque

2

Apparent motor current
(MCTRL1−IMOT)

3 V/6 mA

º rated inverter current

3

DC−bus voltage (MCTRL1−DCVOLT)

6 V/12 mA

º DC 1000 V (400 V

mains)
6 V/12 mA

º DC 380 V (240 V

mains)

4

Motor power

3 V/6 mA

º rated motor power

5

Motor voltage (MCTRL1−VOLT)

4.8 V/9.6 mA

º rated motor

voltage

6

1/output frequency (1/C0050)
(MCTRL1−1/NOUT)

2 V/4 mA

º 0.5 ´ C0011

7

Output frequency within adjusted
limits (DCTRL1−C0010...C0011)

0 V/0 mA/4 mA

º f = f

min

(C0010)

6 V/12 mA

º f = f

max

(C0011)

8

Operation with process controller
(C0238= 0, 1):
Actual process controller value
(PCTRL1−ACT)

6 V/12 mA

º C0011

Operation without process controller
(C0238 = 2):
Output frequency without slip
(MCTRL1−NOUT)

9

Ready for operation (DCTRL1−RDY)

Selection 9 ... 25 corresponds to
the digital functions of the relay
output K1 or the digital switching
output K1 (C0008) or the digital
output A1 (C0117):
LOW = 0 V/0 mA/4 mA
HIGH = 10 V/20 mA

10

TRIP error message (DCTRL1−TRIP)

11

Motor is running (DCTRL1−RUN)

12

Motor is running / CW rotation
(DCTRL1−RUN−CW)

13

Motor is running / CCW rotation
(DCTRL1−RUN−CCW)

14

Output frequency = 0
(DCTRL1−NOUT=0)

15

Frequency setpoint reached
(MCTRL1−RFG1=NOUT)

16

Values have fallen below frequency
threshold Q

min

(f < C0017)

(PCTRL1−QMIN)

LOW active

17

I

max

limit reached (MCTRL1−IMAX)

C0014 = −5−: Torque setpoint reached

18

Overtemperature (

ϑ

max

− 5 °C)

(DCTRL1-OH-WARN)

19

Values have fallen below TRIP or Q

min

or pulse inhibit (IMP) is active
(DCTRL1−TRIP−QMIN−IMP)

20

PTC warning (DCTRL1−PTC−WARN)

Advertising