2 mains connection, Mains connection, Electrical installation – Lenze E82xVxxxKxxxxx User Manual

Page 143: Stop

Advertising
background image

Electrical installation

Standard devices in the power range 15 ... 30 kW

Mains connection

6

l

143

EDS82EV903 EN 3.0

6.6.2

Mains connection

(

Stop!

ƒ

Only connect the controller to the permitted mains voltage (

^ Technical

data). A higher mains voltage destroys the controller!

ƒ

Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.

ƒ

The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.

PE

L1

L2

L3

+UG

-UG

l

0

L1, L2, L3

+UG, -UG

PE

5 Nm

44 lb-in

M6

3/PE AC 400V

1

L1

L2
L3

N
PE

+UG

-UG

Z1

PE

L1

L2

L3

3/PE AC 400V

T2

T1

L2 L3

L1

PE

2

3

3

3

3

4

4

PE L1’

L2’

L3’

Gerät / Load

Z1

PE

L1

L2

L3

+UG

-UG

l

L1, L2, L3

+UG, -UG

PE

5 Nm

44 lb-in

M6

PE

PE

L1

L2

L3

+UG

-UG

l

+UG, -UG
PE

M6

5 Nm
44 lb-in

3/PE AC 400V

T1
T2

2,5 Nm

22.1 lb-in

L1 L2 L3

L1, L2,
L3

2-5 Nm
17.7-44.3 lb-in

PE

J>

8200vec288

Fig. 6−18

Mains connection 15 ... 30 kW

0

Connection for mains choke

1

Connection for footprint mains filter

2

Connection for built−on mains filter

3

Connection for braking unit

^ Documentation of braking unit)

4

Temperature monitoring connection for mains filter (thermal contact

Z1

Mains choke/mains filter