Function library

Free interconnection of analog signals
Free configuration of analog outputs

10

l

332

EDS82EV903 EN 3.0

10.11.2

Free configuration of analog outputs

Description

ƒ

The analog outputs (X3/62, X3/63) and the frequency output (X3/A4) can be freely
assigned to internal analog process signals or monitoring signals. The controller
outputs a voltage proportional to the internal signal at the analog outputs.

ƒ

Currents can also be output when using the application I/O.
– Range: 0 ... 20 mA, as of software version 1.1 also 4 ... 20 mA
– Setting via jumper at module and C0424

ƒ

A signal source can be assigned to several targets.

)

Note!

Use C0111 to permanently assign the analog output X3/62 to some internal
signal sources. C0419/1 is automatically adapted.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0419

v

Free
configuration
of analog
outputs

Output of analog signals to terminal

^ 332

1 X3/62

(AOUT1−IN)

0

Output frequency
(MCTRL1−NOUT+SLIP)

A selection in C0111 is copied into
C0419/1. Change of C0419/1 sets
C0111 = 255!

2

(A)

X3/63
(AOUT2−IN)

2

Apparent motor current
(MCTRL1−IMOT)

3

(A)

X3/A4
(DFOUT1−IN)

3

DC−bus voltage (MCTRL1−DCVOLT)

Frequency output: 50 Hz ... 10 kHz