Technical data – Lenze E82xVxxxKxxxxx User Manual

Page 46

Advertising
background image

Technical data

Operation with rated power (normal operation)
Rated data for 500 V mains voltage

4

l

46

EDS82EV903 EN 3.0

Typical motor power
Three−phase asynchronous
motor (4−pole)

P

rated

[kW]

3.0

4.0

5.5

P

rated

[hp]

4.0

5.0

7.5

8200 vector type

EMC filter integrated

E82xV302K4C0xx

E82xV402K4C0xx

E82xV552K4C0xx

Without EMC filter

E82xV302K2C4xx

E82xV402K4C2xx

E82xV552K4C2xx

Rated mains current at a
switching frequency of 8 kHz
(Lenze setting)

without mains choke

I

mains

[A]

7.2

9.8

13.4

with mains choke

I

mains

[A]

5.6

7.0

9.6

Output power +U

DC

, −U

DC

1)

P

DCres

[kW]

1.7

0.8

1.1

Rated output
current at
switching
frequency

2 kHz sin

I

r

[A]

5.8

7.6

10.4

4 kHz sin

8 kHz sin

I

r

[A]

5.8

7.6

10.4

16 kHz sin

2)

I

r

[A]

3.8

4.9

6.8

Max. permissible
output current for
60 s at switching
frequency

2 kHz sin

I

max

[A]

11.0

14.2

19.5

4 kHz sin

8 kHz sin

I

max

[A]

11.0

14.2

19.5

16 kHz sin

2)

I

max

[A]

5.7

7.9

10.0

Power loss (operation with I

N8

)

E82EV...

P

loss

[W]

145

180

230

E82DV... inside/outside

P

loss

[W]

48/97

60/120

77/153

E82CV... inside/cooler

P

loss

[W]

48/97

60/120

77/153

Dimensions

Dependent on the mounting variant (

^ 61)

Mass

E82EV...

m [kg]

2.9

E82DV...

m [kg]

2.9

E82CV...

m [kg]

2.4

1)

Power supplied by the DC bus when operating with power−adapted motor

2)

Switching frequency is reduced to 4 kHz if

J reaches max. − 5 °C

Advertising