Technical data – Lenze E82xVxxxKxxxxx User Manual
Page 46
![background image](/manuals/566070/46/background.png)
Technical data
Operation with rated power (normal operation)
Rated data for 500 V mains voltage
l
46
EDS82EV903 EN 3.0
Typical motor power
Three−phase asynchronous
motor (4−pole)
P
rated
[kW]
3.0
4.0
5.5
P
rated
[hp]
4.0
5.0
7.5
8200 vector type
EMC filter integrated
E82xV302K4C0xx
E82xV402K4C0xx
E82xV552K4C0xx
Without EMC filter
E82xV302K2C4xx
E82xV402K4C2xx
E82xV552K4C2xx
Rated mains current at a
switching frequency of 8 kHz
(Lenze setting)
without mains choke
I
mains
[A]
7.2
9.8
13.4
with mains choke
I
mains
[A]
5.6
7.0
9.6
Output power +U
DC
, −U
DC
1)
P
DCres
[kW]
1.7
0.8
1.1
Rated output
current at
switching
frequency
2 kHz sin
I
r
[A]
5.8
7.6
10.4
4 kHz sin
8 kHz sin
I
r
[A]
5.8
7.6
10.4
16 kHz sin
2)
I
r
[A]
3.8
4.9
6.8
Max. permissible
output current for
60 s at switching
frequency
2 kHz sin
I
max
[A]
11.0
14.2
19.5
4 kHz sin
8 kHz sin
I
max
[A]
11.0
14.2
19.5
16 kHz sin
2)
I
max
[A]
5.7
7.9
10.0
Power loss (operation with I
N8
)
E82EV...
P
loss
[W]
145
180
230
E82DV... inside/outside
P
loss
[W]
48/97
60/120
77/153
E82CV... inside/cooler
P
loss
[W]
48/97
60/120
77/153
Dimensions
Dependent on the mounting variant (
^ 61)
Mass
E82EV...
m [kg]
2.9
E82DV...
m [kg]
2.9
E82CV...
m [kg]
2.4
1)
Power supplied by the DC bus when operating with power−adapted motor
2)
Switching frequency is reduced to 4 kHz if
J reaches max. − 5 °C