4 fuses and cable cross-sections according to ul, Fuses and cable cross−sections according to ul, Electrical installation – Lenze E82xVxxxKxxxxx User Manual

Page 137: Operation with increased rated power

Advertising
background image

Electrical installation

Standard devices in a power range from 3 ... 11 kW

Fuses and cable cross−sections according to UL

6

l

137

EDS82EV903 EN 3.0

Operation with increased rated power

8200 vector

Rated fuse current

Cable cross−section

ELCB

1)

Fuse

Circuit−breaker

Laying system L1, L2, L3, N, PE

B2

C

Type

[A]

[A]

[mm

2

]

[mm

2

]

[mA]

Mains 3/PE AC 230/240 V − operation without mains choke/mains filter

E82xV302K2C

25

B25

6

4)

³ 300

2)

³ 30

3)

E82xV552K2C

Operation only permitted with mains choke or mains filter

E82xV302K2C

16

B16

2.5

³ 300

2)

³ 30

3)

E82xV402K2C

20

B20

4

E82xV552K2C

B25

6

4

)

E82xV752K2C

B32

6

4

)

E82xV302K2C

20

B20

4

³ 300

2)

³ 30

3)

E82xV552K2C

32

B32

6

4)

Mains 3/PE AC 400 V − operation without mains choke/mains filter

E82xV302K4C

16

B16

2.5

³ 300

2)

³ 30

3)

E82xV402K4C

Operation only permitted with mains choke or mains filter

E82xV752K4C

Mains 3/PE AC 400 V − operation with mains choke/mains filter

E82xV302K4C

10

B10

1.5

³ 300

2)

³ 30

3)

E82xV402K4C

16

B16

2.5

E82xV752K4C

B20

4

1)

Earth−leakage circuit breaker

2)

Is used with E82EVxxxKxC0xx (with integrated EMC filter)

3)

Is used with E82EVxxxKxC2xx (without integrated EMC filter)

4)

Pin−end connector required

6.5.4

Fuses and cable cross−sections according to UL

Supply conditions

Range

Description

Fuses

l

Only in accordance with UL 248

l

System short−circuit current up to 5000 A

rms

: All classes are permissible

l

System short−circuit current up to 50000 A

rms

: Only classes "CC", "J", "T" or "R" permissible

Circuit−brea
ker

l

Only in accordance with UL 489

l

Manufacturer/type
– ABB: S 200 U Charact. K
– Schneider Electric: Multi9 C60 Charact. C
– Moeller: FAZ−C Charact. C

Cables

l

Only in accordance with UL

l

The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C

Observe all national and regional regulations!