Function library

Configuration of analog and digital setpoints and actual values
Digital setpoints via frequency input

10

l

306

EDS82EV903 EN 3.0

Adjustment

1. In C0425, enter the frequency, resolution, scanning time and type of setpoint signal

(single−track, two−track) (C0425).

2. In C0426, select a gain which ensures that the input frequency corresponds to the

normalisation frequency at maximum process motor speed.
– The gain always acts both on the setpoint signal and the offset.
– 100 % corresponds to a gain factor = 1.

C0426 +

f

N

@ p

z @ C0011 @ 100 %

f

r

Normalisation frequency from C0425

p

Pole pair number of the motor

z

Number of encoder increments

C0011

Maximum output frequency (corresponds to
maximum process motor speed)

3. Set offset if required (C0427).

– An offset will shift the characteristic.

Setting tips

ƒ

In case of higher accuracy requirements, select a higher resolution in C0425.

ƒ

A two−track frequency signal serves to evaluate the direction of rotation of the
motor.

)

Note!

The setting for the minimum output frequency (C0010) is not effective.