Electrical installation

Standard devices in the power range 15 ... 30 kW

Connection relay outputs K1 and K2

6

l

147

EDS82EV903 EN 3.0

6.6.6

Connection relay outputs K1 and K2

K14

K1

K2

K12

K11

K24

nc

K11

K21

K12

K22

X1.2

X1.3

K14

K24

nc

K22

K21

8200vec261

Fig. 6−20

Relay connections K1 and K2

Relay K1

Function

Relay position

switched

Message

(Lenze setting)

Technical data

X1.2/K11

Relay output
normally−closed
contact

opened

TRIP

250 VAC/3 A

DC 24 V/2 A ... DC 240 V/0.22 A

X1.2/K12

Relay mid−position
contact

X1.2/K14

Relay output
normally−open
contact

closed

TRIP

PES

HF shield termination by PE connection through shield clamp

)

Note!

ƒ

Switching of control signals:
– Use shielded cables
– HF shield termination by PE connection
– The minimum load for switching the signals through correctly is 12 V and

5 mA. Both values have to be exceeded at the same time.

ƒ

Switching of mains potentials:
– Unshielded cables are sufficient

ƒ

For the protection of the relay contacts a corresponding suppressor circuit is
absolutely required for an inductive or a capacitive load!

ƒ

The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.

ƒ

The message that is output can be changed in code C0008 or C0415/1.