Mechanical installation – Lenze E82xVxxxKxxxxx User Manual

Page 64

Advertising
background image

Mechanical installation

Standard devices in a power range from 0.25 ... 2.2 kW
Thermally separated mounting (push−through technique)

5

l

64

EDS82EV903−3.0

Mounting

3.

3.

2.

1.

1.

4.

5.

E82DV_001

Fig. 5−3

Thermally separated mounting 0.25 ... 0.75 kW

1. Slide on frame.

2. Insert seal.

3. Slide earthing clamps on the frame with the correct sides:

– The contact springs have to point towards the rear panel of the control cabinet.
– The cutouts of the seal specify the positions.

4. Insert 8200 vector into cutout.

5. Tighten by means of 8 screws M4x10.

– Tightening torque: 1.7 Nm (15 lb−in)