Lenze E82xVxxxKxxxxx User Manual

Page 496

Advertising
background image

Safety engineering

Safety relay K

SR

14

l

496

EDS82EV903 EN 3.0

Wiring

}

Danger!

Faulty operation in case of earth faults possible
The correct functioning of the safety function is not ensured if an earth fault
occurs.
Possible consequences:

ƒ

A failure of the safety function can lead to death, severe injuries or damage
to material.

Protective measures:
The electrical reference point for the coil of the safety relay K

SR

must be

connected to the PE conductor system (EN 60204−1, paragraph 9.4.3)!

}

Danger!

Danger to life through improper installation
Improper installation of the safety engineering systems may cause an
uncontrolled starting action of the drives.
Possible consequences:

ƒ

Death, severe injuries, or damage to material assets during an uncontrolled
starting action of the drives.

Protective measures:

ƒ

Shielded installation of all control cables connected to the FIF module is
essential to reduce interference injection.

ƒ

Apply the shield to a large surface of the EMC sheet.

Advertising