Electrical installation – Lenze E82xVxxxKxxxxx User Manual

Page 138

Advertising
background image

Electrical installation

Standard devices in a power range from 3 ... 11 kW
Fuses and cable cross−sections according to UL

6

l

138

EDS82EV903 EN 3.0

Operation at rated power

8200 vector

Rated fuse current / cable cross−section

Fuse

Circuit−breaker

Type

L1, L2, L3, N, PE

Type

L1, L2, L3, N, PE

Type

[A]

[AWG]

[A]

[AWG]

Mains 3/PE AC 230/240 V − operation without mains choke/mains filter

E82xV302K2C

20

12

E82xV402K2C

25

10

E82xV552K2C

30

8

4

)

E82xV752K2C

Operation only permitted with mains choke or mains filter

Mains 3/PE AC 230/240 V − operation with mains choke/mains filter

E82xV302K2C

20

12

E82xV402K2C

25

10

E82xV552K2C

35

E82xV752K2C

35

8

4

)

Mains 3/PE AC 400/500 V − operation without mains choke/mains filter

E82xV302K4C

15

14

E82xV402K4C

15

14

E82xV552K4C

20

12

E82xV752K4C

25

10

E82xV113K4C

Operation only permitted with mains choke or mains filter

Mains 3/PE AC 400/500 V − operation with mains choke/mains filter

E82xV302K4C

10

16

E82xV402K4C

15

14

E82xV552K4C

20

12

E82xV752K4C

25

10

E82xV113K4C

25

10

4)

Pin−end connector required

Operation with increased rated power

Operation at an increased rated power is not UL−certified.