Function library
Code table
l
404
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0245
*
v
(A)
Comparison
value selection
for
MSET1=MACT
0
0
MCTRL1−MSET (C0412/6 or C0047)
Comparison value selection for
setting the digital output signal
MSET1=MACT (torque threshold 1
= actual torque value)
l
If the difference between
MCTRL1−MSET1 and
MCTRL1−MACT or C0250 is
within C0252:
– MSET1=MACT = HIGH after
expiration of the time set in
C0254
1
Value in C0250
C0250
*
(A)
Torque
threshold 1
(MCTRL1−
MSET1)
0.0
−200.0
{0.1 %}
200.0 Based on rated motor torque
C0251
*
(A)
Torque
threshold 2
(MCTRL1−
MSET2)
0.0
−200.0
{0.1 %}
200.0 Based on rated motor torque
Comparison value selection for
setting the digital output signal
MSET2=MACT (torque threshold 2
= actual torque value)
l
If the difference between
MCTRL1−MSET2 and
MCTRL1−MACT is within
C0253:
– MSET2=MACT = HIGH after
expiration of the time set in
C0255
C0252
*
(A)
Differential
threshold for
MSET1=MACT
0.0
0.0
{0.1 %}
100.0
C0253
*
(A)
Differential
threshold for
MSET2=MACT
0.0
0.0
{0.1 %}
100.0
C0254
*
(A)
Deceleration
MSET1=MACT
0.000 0.000
{0.001 s}
65.000 "Debouncing" of digital output
signal MSET1=MACT
l
Sets MSET1=MACT = HIGH if
the following still holds true
after expiration of the set time:
– Difference between
MCTRL1−MSET1 and
MCTRL1−MACT or C0250 is
within operating threshold
C0252
l
Transition HIGH
ð LOW
without deceleration
C0255
*
(A)
Deceleration
MSET2=MACT
0.000 0.000
{0.001 s}
65.000 "Debouncing" of digital output
signal MSET2=MACT
l
Sets MSET2=MACT = HIGH if
the following still holds true
after expiration of the set time:
– Difference between
MCTRL1−MSET2 and
MCTRL1−MACT is within
operating threshold C0253
l
Transition HIGH
ð LOW
without deceleration