1 start conditions/flying-restart circuit, Start conditions/flying−restart circuit, Function library – Lenze E82xVxxxKxxxxx User Manual

Page 275

Advertising
background image

Function library

Behaviour in the event of mains switching, mains failure or controller inhibit

Start conditions/flying−restart circuit

10

l

275

EDS82EV903 EN 3.0

10.4

Behaviour in the event of mains switching, mains failure or controller inhibit

10.4.1

Start conditions/flying−restart circuit

Description

Determines the controller behaviour after a restart after controller inhibit, mains
switching or a mains failure.

With activated flying−restart circuit the controller automatically synchronises to a
coasting motor after mains disconnection or adds a setpoint signal.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0142

v

Starting
condition

1

0

Automatic start is inhibited after
mains connection
Flying restart circuit inactive

Start after HIGH−LOW−HIGH level
change at X3/28

^ 275

1

Automatic start if X3/28 = HIGH
Flying restart circuit inactive

2

Automatic start is inhibited after
mains connection
Flying restart circuit active

Start after HIGH−LOW−HIGH level
change at X3/28

3

Automatic start if X3/28 = HIGH
Flying restart circuit active

C0143
*

v

Selection of
flying restart
mode

0

0

Max. output frequency (C0011) ... 0 Hz

Motor speed is searched for in the
stated range

^ 275

1

Last output frequency ... 0 Hz

2

Connect frequency setpoint
(NSET1−NOUT)

The respective value is connected
after the controller enable

3

Connect actual process controller value
(C0412/5) (PCTRL1−ACT)

Drive behaviour without flying−restart circuit

Manual start (C0142 = 0):

After mains interruption the drive only restarts after a LOW/HIGH level change at the
"Controller inhibit" terminal (X3/28).

Automatic start (C0142 = 1)

After mains interruption the drive only restarts if a HIGH level is applied to the "controller
inhibit"terminal (X3/28).

The controller sets all integrators to zero and releases them again.

Drive behaviour with flying−restart circuit

Manual start with flying−restart circuit (C0142 = 2)

After mains interruption the drive only restarts after a LOW/HIGH level change at the
"Controller inhibit" terminal (X3/28).

Automatic start with flying−restart circuit (C0142 = 3)

After mains interruption the drive only restarts if a HIGH level is applied to the "controller
inhibit"terminal (X3/28).