Electrical installation – Lenze E82xVxxxKxxxxx User Manual

Page 116

Advertising
background image

Electrical installation

Basics for wiring according to EMC
Shielding

6

l

116

EDS82EV903 EN 3.0

Control cables

ƒ

The cables of the analog and digital inputs and outputs must be shielded. Short (up
to 200 mm), unshielded cables must always be twisted.

ƒ

Analog cables: Place one side of the shield on the inverter.

ƒ

To achieve an optimum shielding effect in unfavourable situations (in case of very
long cables, with high interference) one shield end can be connected to PE potential
via a capacitor (e.g. 10 nF/250 V) (see sketch).

ƒ

Digital cables: Place both sides of the shield on the inverter.

ƒ

The shield connections of the control cables must have a distance of at least 50 mm
to the shield connections of the motor and DC cables.

9300vec043

Fig. 6−4

Shielding of long, analog control cables