Function library

Automatic detection of motor data

10

l

315

EDS82EV903 EN 3.0

10.8

Automatic detection of motor data

Description

This function serves to determine the required motor data and influences of the motor
cable.

Must be carried out prior to initial commissioning of the vector control (C0014 = 4) or the
sensorless torque control (C0014 = 5). Otherwise commissioning will not be possible.

)

Note!

The motor data identification also influences the smooth running
performance in the "V/f characteristic control with constant V

min

boost"

operating mode (C0014 = 2 or 3). If motor data identification is carried out in
this operating mode, the smooth running performance can be optimised for
lower speeds.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0084 Motor stator

resistance

0.000 0.000

{0.001

W}

64.000

^ 315

0.0

0.0

{0.1

m

W}

6500.0 Only 8200 vector 15 ... 90 kW

C0087 Rated motor

speed

à

300

{1 rpm}

16000

à

Device−dependent

^ 315

C0088 Rated motor

current

à

0.0

0.1 (A)

650.0

à

Device−dependent

0.0 ... 2.0 x rated output current of
the controller

^ 315

C0089 Rated motor

frequency

50

10

{1 Hz}

960

^ 315

C0090 Rated motor

voltage

à

50

{1 V}

500

à

230 V for 230 V controllers,
400 V for 400 V controllers

^ 315

C0091 Motor cos

ϕ

а

0.40

{0.1}

1.0

а

Device−dependent

^ 315

C0092 Motor stator

inductance

0.0

0.000

{0.1 mH} Device−dependent

^ 315

0.00

0.00

{0.01

mH}

Device−dependent Only 8200 vector 15 ... 90 kW

C0148
*

s

Identifying
motor data

0

0

Ready

Only when the motor is cold!
1. Inhibit controller, wait until

drive is at standstill

2. Enter the correct values from

the motor nameplate in C0087,
C0088, C0089, C0090, C0091

3. Set C0148 = 1, confirm with

v

4. Enable controller:

The identification
– starts,

c goes out

– the motor "whistles" faintly

but it does not rotate!

– takes approx. 30 s
– is completed when

c is lit

again

5. Inhibit controller

^ 315

1

Start identification

l

V/f rated frequency (C0015), slip
compensation (C0021) and motor
stator inductance (C0092) are
calculated and saved

l

The motor stator resistance (C0084)
= total resistance of the motor cable
and motor is measured and saved