Electrical installation

Standard devices in a power range from 0.25 ... 2.2 kW
Fuses and cable cross−sections according to EN 60204−1

6

l

124

EDS82EV903 EN 3.0

Controller of type E82xVxxxK4C (400/500 V mains)

(

Stop!

ƒ

Only connect the controller to the permitted mains voltage (

^ Technical

data). A higher mains voltage destroys the controller!

ƒ

Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.

ƒ

The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.

E82EV551K4C

E82EV751K4C

E82EV152K4C

E82EV222K4C

X1.1

X1.1

L2

PE

L1

L2

L3

3/PE AC 400 V

+UG -UG

L1

L3 PE

8200vec011

Fig. 6−9

Mains connection 400/500 V 0.55 ... 2.2 kW

X1.1/+UG,
X1.1/−UG

Supply for DC−bus operation

6.4.3

Fuses and cable cross−sections according to EN 60204−1

Supply conditions

Range

Description

Fuses

l

Utilisation category: only gG/gL or gRL

Cables

Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).

RCCB

l

Controllers can cause a DC current in the PE conductor. If a residual current device (RCD) or a
fault current monitoring unit (RCM) is used for protection in the case of direct or indirect
contact, only one RCD/RCM of the following type can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for connection to a

1−phase system

Alternatively another protective measure can be used, like for instance isolation from the
environment by means of double or reinforced insulation, or isolation from the supply system
by using a transformer.

l

Earth−leakage circuit breakers must only be installed between mains supply and controller.

Observe all national and regional regulations!