Commissioning

Important codes for quick commissioning

8

l

220

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0037 JOG1

20.00 −650.00

{0.02

Hz}

650.00 JOG = fixed setpoint

Additional fixed setpoints

ðC0440

^ 309

C0038 JOG2

30.00 −650.00

{0.02

Hz}

650.00

C0039 JOG3

40.00 −650.00

{0.02

Hz}

650.00

C0050
*

uSEr

Output freq.
(MCTRL1−
NOUT)

−650.00

{Hz}

650.00 Read only: Output frequency

without slip compensation

C0087 Rated motor

speed

à

300

{1 rpm}

16000

à

Device−dependent

^ 315

C0088 Rated motor

current

à

0.0

0.1 (A)

650.0

à

Device−dependent

0.0 ... 2.0 x rated output current of
the controller

^ 315

C0089 Rated motor

frequency

50

10

{1 Hz}

960

^ 315

C0090 Rated motor

voltage

à

50

{1 V}

500

à

230 V for 230 V controllers,
400 V for 400 V controllers

^ 315

C0091 Motor cos

ϕ

а

0.40

{0.1}

1.0

а

Device−dependent

^ 315

C0119

v

Configuration
of motor
temperature
monitoring
(PTC input) /
earth fault
detection

0

0

PTC input inactive

Earth fault
detection active

l

Configure signal output in
C0415

l

If several parameter sets are
used, monitoring has to be set
separately for every parameter
set.

l

Deactivate earth fault detection
if the earth fault detection is
actuated unintentionally.

l

If the earth fault detection is
activated, the motor starts with
a delay of approx. 40 ms after
controller enable has been set.

^ 359

1

PTC input active,
TRIP effected

2

PTC input active,
warning effected

3

PTC input inactive

Earth fault
detection inactive

4

PTC input active,
TRIP effected

5

PTC input active,
warning effected

C0140
*

Additive
frequency
setpoint
(NSET1−NADD)

0.00

−650.00

{0.02

Hz}

650.00

l

Selection via

j function of

the keypad or parameter
channel

l

Acts additively on the main
setpoint

l

Value will be stored when
switching the mains or
removing the keypad

l

C0140 is only transferred
during parameter set transfer
with GDC (not with keypad)

^ 311

C0148
*

s

Identifying
motor data

0

0

Ready

Only when the motor is cold!
1. Inhibit controller, wait until

drive is at standstill

2. Enter the correct values from

the motor nameplate in C0087,
C0088, C0089, C0090, C0091

3. Set C0148 = 1, confirm with

v

4. Enable controller:

The identification
– starts,

c goes out

– the motor "whistles" faintly

but it does not rotate!

– takes approx. 30 s
– is completed when

c is lit

again

5. Inhibit controller

^ 315

1

Start identification

l

V/f rated frequency (C0015), slip
compensation (C0021) and motor
stator inductance (C0092) are
calculated and saved

l

The motor stator resistance (C0084)
= total resistance of the motor cable
and motor is measured and saved