Technical data – Lenze E82xVxxxKxxxxx User Manual

Page 59

Advertising
background image

Technical data

Operation with increased rated power

Rated data for 400 V mains voltage

4

l

59

EDS82EV903 EN 3.0

Typical motor power
Three−phase asynchronous
motor (4−pole)

P

rated

[kW]

90

110

P

rated

[hp]

125

150

8200 vector type

With mains filter

E82xV753K4B3xx

Without mains filter

E82xV753K4B2xx

2)

E82xV903K4B2xx

2)

3)

Rated mains current

without mains choke/mains

filter

I

mains

[A]

With mains choke/mains filter

I

mains

[A]

144

185

Output power +U

DC

, −U

DC

1)

P

DCres

[kW]

28.1

40.8

Rated output
current at
switching
frequency

1 kHz sin

I

r

[A]

150

159

4)

2 kHz sin

4 kHz sin

1 kHz

I

r

[A]

159

205

2 kHz

4 kHz

Max. permissible
output current for
60 s at switching
frequency

1 kHz sin

I

max

[A]

225

238

4)

2 kHz sin

4 kHz sin

1 kHz

I

max

[A]

225

270

2 kHz

4 kHz

Power loss (operation with I

N8

)

E82EV...

P

loss

[W]

1960

2400

E82DV... inside/outside

P

loss

[W]

653/1307

800/1600

E82VV... inside/cooler

P

loss

[W]

Dimensions

Dependent on the mounting variant (

^ 61)

Mass with mains
filter

E82EV...

m [kg]

112

E82DV...

m [kg]

112

E82CV...

m [kg]

Mass without
mains filter

E82EV...

m [kg]

59

E82DV...

m [kg]

59

E82CV...

m [kg]

1)

Power supplied by the DC bus when operating with power−adapted motor

2)

Operation only permitted with mains choke (

^ 106)

3)

Max. permissible operating ambient temperature +35 °C

4)

Only operate with automatic switching frequency reduction (C144 = 1). Ensure that the specified current values are
not exceeded.