Free interconnection of analog signals
Free configuration of analog process data output words

10

l

340

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0421
*

v
(Cont.)

Possible analog signals for C0421

Selection 9 ... 25 corresponds to
the digital functions of relay
output K1 (C0008) or digital
output A1 (C0117):
LOW = 0
HIGH = 1023

^ 338

9

Ready for operation (DCTRL1−RDY)

10

TRIP error message (DCTRL1−TRIP)

11

Motor is running (DCTRL1−RUN)

12

Motor is running / CW rotation
(DCTRL1−RUN−CW)

13

Motor is running / CCW rotation
(DCTRL1−RUN−CCW)

14

Output frequency = 0
(DCTRL1−NOUT=0)

15

Frequency setpoint reached
(DCTRL1−RFG1=NOUT)

16

Values have fallen below frequency
threshold Q

min

(f < C0017)

(PCTRL1−QMIN)

17

I

max

limit reached (MCTRL1−IMAX)

C0014 = −5−: Torque setpoint reached

18

Overtemperature (

J

max

−5 °C)

(DCTRL1-OH-WARN)

19

TRIP or Q

min

or pulse inhibit (IMP)

(DCTRL1−IMP)

20

PTC warning (DCTRL1−PTC−WARN)

21

Apparent motor current < current
threshold (DCTRL1−IMOT<ILIM)

V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q

min

= C0017

22

Apparent motor current < current
threshold and output frequency >
Frequency threshold Q

min

(DCTRL1−(IMOT<ILIM)−QMIN)

23

Apparent motor current < current
threshold and ramp function generator
1: input = output
(DCTRL1−(IMOT<ILIM)−RFG−I=0)

24

Motor phase failure warning
(DCTRL1−LP1−WARN)

25

Min. output frequency reached
(f

£ C0010) (PCTRL1−NMIN)