Electrical installation

Standard devices in a power range from 3 ... 11 kW
Mains connection

6

l

134

EDS82EV903 EN 3.0

Controller of type E82xVxxxK4C (400/500 V mains)

(

Stop!

ƒ

Only connect the controller to the permitted mains voltage (

^ Technical

data). A higher mains voltage destroys the controller!

ƒ

Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.

ƒ

The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.

X1.1

3 PE AC 400 V

45 Hz -0 %...65 Hz +0 % 320 V -0 %...550 V +0 %

X1.1

PE L1

L3

+UG -UG

L2

E82EVXXXK4C

L1
L2
L3

N

PE

0,7...0,8 Nm
6.2...7.1 lb-in

6 mm / 0.24 in

8200vec067

Fig. 6−14

Mains connection 400/500 V controller 3 ... 11 kW

X1.1/+UG,
X1.1/−UG

Supply for DC−bus operation