DC−bus operation

Fuses and cable cross−sections

Mains supply

12

l

467

EDS82EV903−3.0

12.5

Fuses and cable cross−sections

12.5.1

Mains supply

)

Note!

The following applies to the mains supply:
The values in the tables refer to the operation of the controllers in a DC−bus
system with P

DC

= 100 %, i.e. utilisation of the max. rated controller power on

DC−bus level. For the operation with lower powers, smaller fuses and cable
cross−sections are possible accordingly.

Installation in accordance with EN 60204−1

Supply conditions

Range

Description

Fuses

l

Utilisation category: only gG/gL or gRL

Cables

Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).

Observe all national and regional regulations!