Function library
Free interconnection of digital signals
Free configuration of digital outputs
l
348
EDS82EV903 EN 3.0
10.12.2
Free configuration of digital outputs
Description
ƒ
The digital outputs (X3/A1, X3/A2, relay output K1, relay output K2) can be freely
assigned to internal digital signals.
ƒ
A signal source can be assigned to several targets.
)
Note!
ƒ
Use C0008 to assign some internal signal sources to the relay output D1.
C0415/1 is automatically adapted.
ƒ
Use C0117 to assign some internal signal sources to the digital output
X3/A1. C0415/2 is automatically adapted.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0415
v
Free
configuration
of digital
outputs
Output of digital signals to terminals
^ 348
1 Relay output
K1 (RELAY,
motec version
151:)
Digital
switching
output K1
(motec version
152, 153)
25
TRIP error message (DCTRL1−TRIP)
A selection in C0008 is copied into
C0415/1. Change of C0415/1 sets
C0008 = 255!
2 Digital output
X3/A1
(DIGOUT1)
16
Ready for operation (DCTRL1−RDY)
A selection in C0117 is copied into
C0415/2. Change of C0415/2 sets
C0117 = 255!
3
(A)
Digital output
X3/A2
(DIGOUT2)
255
Not assigned (FIXED−FREE)