Function library

Free interconnection of digital signals

Free configuration of digital outputs

10

l

349

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0415

v
(Cont.)

Possible digital signals for C0415

^ 348

0

Not assigned (FIXED−FREE)

1

Parameter set 2 or parameter set 4 is
active (DCTRL1−PAR−B0)

PAR−B1 PAR−B0
LOW

LOW

LOW

HIGH

HIGH

LOW

HIGH

HIGH

Active
PAR1
PAR2
PAR3
PAR4

2

Pulse inhibit active (DCTRL1−IMP)

3

I

max

limit reached (MCTRL1−IMAX)

(C0014 = −5−: torque setpoint reached)

4

Frequency setpoint reached
(DCTRL1−RFG1=NOUT)

5

Ramp function generator 1: input =
output (NSET1−RFG1−I=O)

RFG1 = ramp function generator −
main setpoint

6

Values have fallen below frequency
threshold Q

min

(f < C0017)

(PCTRL1−QMIN)

LOW active

7

Output frequency = 0
(DCTRL1−NOUT=0)

8

Controller inhibit active (DCTRL1−CINH)

9...12

Reserved

13

Group signal
(DCTRL1−OH−PTC−LP1−FAN1−WARN):
Warning − overtemperature (

J

max

− 5

°C) (DCTRL1−OH−WARN)
or
Warning − motor overtemperature
(DCTRL1−LP1−PTC−WARN)
or

Set C0119 = 2 or C0119 = 5

Motor phase failure warning
(DCTRL1−LP1−WARN)
or

Set C0597 = 2

Warning − fan failure
(only active with 8200 motec)

With 8200 vector, C0608 must be
set to 0

14

DC bus overvoltage (DCTRL1−OV)

15

CCW rotation (DCTRL1−CCW)

16

Ready for operation (DCTRL1−RDY)

17

Parameter set 3 or parameter set 4
active (DCTRL1−PAR−B1)

PAR−B1 PAR−B0
LOW

LOW

LOW

HIGH

HIGH

LOW

HIGH

HIGH

Active
PAR1
PAR2
PAR3
PAR4

18

Values have fallen below TRIP or Q

min

or pulse inhibit (IMP) is active
(DCTRL1−TRIP−QMIN−IMP)

19

PTC warning (DCTRL1−PTC−WARN)

Set C0119 = 2 or C0119 = 5

Status of relay K

SR

Only with 8200 vector 15 ...90 kW,
variant "safe standstill":
HIGH = pulse inhibit active by
"safe standstill"
LOW = no pulse inhibit by "safe
standstill"