Function library – Lenze E82xVxxxKxxxxx User Manual

Page 295

Advertising
background image

Function library

Acceleration, deceleration, braking, stopping

AC motor braking

10

l

295

EDS82EV903 EN 3.0

Adjustment

Parameter

Code

Setting parameter set 1
(active during normal operation)

Setting parameter set 2
(active during braking operation)

Switching threshold

C0988

Set C0988 depending on the mains voltage:

AC 230 V

ð C0988 = 112 %

AC 400 V

ð C0988 = 112 %

AC 440 V

ð C0988 = 123 %

AC 460 V

ð C0988 = 129 %

AC 480 V

ð C0988 = 134 %

AC 500 V

ð C0988 = 140 %

V/f rated frequency

C0015

Value adapted to the drive, e.g. 50 Hz

Depending on the drive power, up to a
minimum of 25 % of the value of C0015
in parameter set 1:

l

General rule: 2.2 kW

ð 50 %

l

Reduce value in case of smaller drive
powers. Increase value in case of
higher drive powers.

That way, the energy in the motor is
reduced due to overexcitation during
operation with parameter set 2.

V

min

boost

C0016

Value adapted to the drive, e.g. 5 %

Depending on the drive power, up to
five times the value of C0016 in
parameter set 1:

l

General rule: 2.2 kW

ð factor 3

l

Reduce factor in case of smaller drive
powers. Increase factor in case of
higher drive powers.

That way, the energy in the motor is
also reduced in the lower speed range
due to overexcitation during operation
with parameter set 2.

Deceleration time for quick stop
during braking along the quick stop
ramp:

C0105

Required braking time for AC braking

Deceleration time of the drive with
max. centrifugal load.
The OU message (overvoltage) must not
be provided during the deceleration.

Deceleration time during the
braking process at the main setpoint
ramp:

C0013

Setting tips

The higher the mains voltage the longer the deceleration time must be set in parameter
set 1 in order to be able to carry out AC motor braking. Hence, braking times with DC
injection brakes are shorter at mains voltages > 400 V.

)

Note!

ƒ

Changeover of the parameter set via terminal, bus or PC is not possible if
C0988 > 0!

ƒ

C0988 is always the same for all parameter sets.

Advertising