Function library, Code table – Lenze E82xVxxxKxxxxx User Manual
Page 410
![background image](/manuals/566070/410/background.png)
Function library
Code table
l
410
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0372
*
Identification
function
module
0
No function module
Display only
1
Standard I/O or AS−i
2
System bus (CAN)
6
Other function module on FIF
e.g. Application I/O, INTERBUS, ...
10
No valid identification
C0395
*
LONGWORD
process input
data
Bits 0 ...
15
Control word of the controller
(mapping to C0135)
Only for bus operation
l
Transmission of control word
and main setpoint in one
telegram to the controller
l
Keypad: read only
(hexadecimal)
Bits 16
... 31
Setpoint 1 (NSET1−N1) (mapping to
C0046)
C0396
*
LONGWORD
process output
data
Bits 0 ...
15
Status word 1 of the controller
(mapping of C0150)
Only for bus operation
l
Reading of status word and
output frequency in one
telegram from the controller
l
Keypad: read only
(hexadecimal)
Bits 16
... 31
Output frequency (MCTRL1−NOUT)
(mapping of C0050)
C0409
v
Configuration −
relay output K2
Output of digital signals to relay K2
l
Relay output K2 only available
with 8200 vector 15 ... 90 kW
l
Only active during operation
with application I/O from
version E82ZAFA...XXVx2x
^ 348
255
255
Not assigned (FIXED−FREE)
Possible digital signals for C0409: see C0415
C0410
v
Free
configuration
of digital input
signals
Linking of digital signal sources to internal
digital signals
A selection in C0007 is copied to
the corresponding subcode of
C0410. A change in C0410 sets
C0007 = 255!
^ 343
1 NSET1−JOG1/3
NSET1−JOG1/3
/5/7 (A)
1
Digital input X3/E1
Selection of fixed
setpoints
C0410/1
C0410/
2
C0410/33
LOW LOW LOW
HIGH LOW LOW
LOW HIGH LOW
...
...
...
HIGH HIGH HIGH
Active
C0046
JOG1
JOG2
...
JOG7
2 NSET1−JOG2/3
NSET1−JOG2/3
/6/7 (A)
2
Digital input X3/E2
3 DCTRL1−CW/
CCW
4
Digital input X3/E4
CW = clockwise
rotation
CCW =
counter−clockwise
rotation
LOW
HIGH
4 DCTRL1−QSP
255
Not assigned (FIXED−FREE)
Quick stop (via terminal
LOW−active)
5 NSET1−RFG1−
STOP
255
Not assigned (FIXED−FREE)
Stop main setpoint of ramp
function generator
6 NSET1−RFG1−0
255
Not assigned (FIXED−FREE)
Set ramp function generator input
for main setpoint to "0"
7 MPOT1−UP
255
Not assigned (FIXED−FREE)
Motor potentiometer functions
8 MPOT1−DOWN
255
Not assigned (FIXED−FREE)
9 Reserved
255
Not assigned (FIXED−FREE)
Do not change 255!
10 DCTRL1−CINH
255
Not assigned (FIXED−FREE)
Controller inhibit (via terminal
LOW−active)
11 DCTRL1−TRIP−
SET
255
Not assigned (FIXED−FREE)
External fault (via terminal
LOW−active)
12 DCTRL1−TRIP−
RESET
255
Not assigned (FIXED−FREE)
Reset fault