Function library, Code table – Lenze E82xVxxxKxxxxx User Manual

Page 410

Advertising
background image

Function library

Code table

10

l

410

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0372
*

Identification
function
module

0

No function module

Display only

1

Standard I/O or AS−i

2

System bus (CAN)

6

Other function module on FIF
e.g. Application I/O, INTERBUS, ...

10

No valid identification

C0395
*

LONGWORD
process input
data

Bits 0 ...
15

Control word of the controller
(mapping to C0135)

Only for bus operation

l

Transmission of control word
and main setpoint in one
telegram to the controller

l

Keypad: read only
(hexadecimal)

Bits 16
... 31

Setpoint 1 (NSET1−N1) (mapping to
C0046)

C0396
*

LONGWORD
process output
data

Bits 0 ...
15

Status word 1 of the controller
(mapping of C0150)

Only for bus operation

l

Reading of status word and
output frequency in one
telegram from the controller

l

Keypad: read only
(hexadecimal)

Bits 16
... 31

Output frequency (MCTRL1−NOUT)
(mapping of C0050)

C0409

v

Configuration −
relay output K2

Output of digital signals to relay K2

l

Relay output K2 only available
with 8200 vector 15 ... 90 kW

l

Only active during operation
with application I/O from
version E82ZAFA...XXVx2x

^ 348

255

255

Not assigned (FIXED−FREE)

Possible digital signals for C0409: see C0415

C0410

v

Free
configuration
of digital input
signals

Linking of digital signal sources to internal
digital signals

A selection in C0007 is copied to
the corresponding subcode of
C0410. A change in C0410 sets
C0007 = 255!

^ 343

1 NSET1−JOG1/3

NSET1−JOG1/3
/5/7 (A)

1

Digital input X3/E1

Selection of fixed
setpoints
C0410/1

C0410/

2

C0410/33

LOW LOW LOW
HIGH LOW LOW
LOW HIGH LOW
...

...

...

HIGH HIGH HIGH

Active
C0046
JOG1
JOG2
...
JOG7

2 NSET1−JOG2/3

NSET1−JOG2/3
/6/7 (A)

2

Digital input X3/E2

3 DCTRL1−CW/

CCW

4

Digital input X3/E4

CW = clockwise
rotation
CCW =
counter−clockwise
rotation

LOW
HIGH

4 DCTRL1−QSP

255

Not assigned (FIXED−FREE)

Quick stop (via terminal
LOW−active)

5 NSET1−RFG1−

STOP

255

Not assigned (FIXED−FREE)

Stop main setpoint of ramp
function generator

6 NSET1−RFG1−0

255

Not assigned (FIXED−FREE)

Set ramp function generator input
for main setpoint to "0"

7 MPOT1−UP

255

Not assigned (FIXED−FREE)

Motor potentiometer functions

8 MPOT1−DOWN

255

Not assigned (FIXED−FREE)

9 Reserved

255

Not assigned (FIXED−FREE)

Do not change 255!

10 DCTRL1−CINH

255

Not assigned (FIXED−FREE)

Controller inhibit (via terminal
LOW−active)

11 DCTRL1−TRIP−

SET

255

Not assigned (FIXED−FREE)

External fault (via terminal
LOW−active)

12 DCTRL1−TRIP−

RESET

255

Not assigned (FIXED−FREE)

Reset fault