Function library

Limit value setting
Speed range

10

l

282

EDS82EV903 EN 3.0

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0010

uSEr

Minimum
output
frequency

0.00

0.00

à

14.5 Hz

{0.02

Hz}

650.00

l

C0010 not effective in the case
of bipolar setpoint selection
(−10 V ... + 10 V)

l

C0010 only limits the analog
input 1

l

In the case of a max. output
frequency > 50 Hz the
switching threshold of the auto
DCB in C0019 has to be
increased.

l

From software 3.5: If
C0010 > C0011, the drive does
not start when controller
enable is set.

à

Speed setting range 1 : 6 for
Lenze geared motors: For
operation with Lenze geared
motors has to be set
necessarily.

^ 281

C0011

uSEr

Maximum
output
frequency

50.00 7.50

à

87 Hz

{0.02

Hz}

650.00

C0239 Lower

frequency
limitation

−650.0

0

−650.00

{0.02

Hz}

650.00

l

The value does not fall below
the limit independently of the
setpoint

l

If the lower frequency
limitation is active, automatic
DC injection braking (auto DCB)
must be deactivated with
C0019 = 0 or C0106 = 0

^ 281

C0236
(A)

Acceleration
time − lower
frequency
limitation

0.00

0.00

{0.02 s}

1300.00 Based on C0011

Lower frequency limitation =
C0239

^ 281

Adjustment

Relationship between output frequency and synchronous motor speed:

n

rsyn

+ C0011 @ 60

p

n

rsyn

Synchronous motor speed [rpm]

C0011

Max. output frequency [Hz]

p

Number of pole pairs (1, 2, 3, ...)

Example:
4−pole asynchronous motor: p = 2, C0011 = 50 Hz

n

rsyn

+ 50 @ 60

2

+ 1500 min

*1