DC−bus operation

Conditions for trouble−free DC−bus operation
Mains connection

12

l

462

EDS82EV903−3.0

Controller protection

Please ensure that all controllers in the DC−bus system are connected simultaneously to the mains
supply.

Starting conditions

Use a central mains contactor (

480)

Decentralised switching of the mains supply is possible if the connection of the individual
contactors is monitored (feedback to PLC) and the contactors are switched with the same
cycle.

A1

A2

An

F4, F5

F1 ... F3

AC

M

M

M

K1

DC

K2

Kn

PLC

K1

K2

Kn

K2

K1

K2

Kn

Z1

Z2

Zn

8200vec650

Fig. 12−1

Decentralised switching of the mains supply in network operation

A1 ... An

Controller 1 ... controller n

F1 ... F3

Mains fuses

F4 ... F5

Fuses on DC level

Z1 ... Zn

Mains choke

K1 ... Kn

Mains contactors

Adapt to the mains voltage

Select the same value for the switching threshold of the brake module / brake chopper for
all controllers in the DC−bus system:

93xx: C0173

8200 vector: C0174

Mains phase failure detection with decentralised supply

Monitor the mains supply for every controller because all active mains input circuits of the
system may be overloaded in the event of a mains failure.

)

Note!

Switch off the entire drive system in the event of a mains failure or mains
phase failure (

480)

Use thermal overcurrent releases for the mains failure detection and reports
(bimetal relays) which are connected downstream of the mains fuses.