Function library

Optimising the operating behaviour

Inverter switching frequency

10

l

271

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0144

v

Temperature−
dependent
reduction of
the switching
frequency

1

0

No temperature−dependent reduction
of the switching frequency

During operation at a switching
frequency of 16 kHz the frequency
is also reduced to 4 kHz. This
behaviour can be changed in
C0310.

^ 270

1

Automatic reduction of the switching
frequency to 4 kHz if

J reaches max. − 5

°C

Automatic switching frequency reduction

C0144 = 0 (no temperature−dependent switching frequency reduction)

If the maximum heatsink temperature (

J

max

is exceeded when using a switching

frequency of 8 kHz or 16 kHz) the inverter will be inhibited, TRIP "OH" (overtemperature)
will be set and the motor will coast to standstill.

C0144 = 1 (temperature−dependent switching frequency reduction is active):

ƒ

If the heatsink temperature

J

max

− 5 °C is reached when using a switching frequency

of 8 kHz or 16 kHz the controller automatically reduces the switching frequency to
4 kHz thus keeping the operation running.

ƒ

After cooling the heatsink the controller automatically changes to the switching
frequency set.

)

Note!

The switching frequency is automatically set to its optimum value depending
on the apparent motor current and output frequency to ensure trouble−free
operation.

ƒ

The noise emission changes.

ƒ

The user cannot influence this function.

Tip

Medium−frequency motors are only allowed to be operated on 8 kHz sin or 16 kHz sin.