DC−bus operation
Conditions for trouble−free DC−bus operation
DC−bus connection
l
464
EDS82EV903−3.0
Fusing
Assign DC−bus fuses to every controller on the side of the DC busbar to protect it against
a defective controller in the DC−bus system.
)
Note!
Two controllers in the DC−bus system:
ƒ
One pair of DC fuses suffices.
ƒ
Rate the fusing depending on the controller with the lower power.
More than two controllers in the DC−bus system:
ƒ
Connect one pair of DC fuses upstream to every controller.
Further information about fusing: (
¶ 474)