Function library

Code table

10

l

386

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0010

uSEr

Minimum
output
frequency

0.00

0.00

à

14.5 Hz

{0.02

Hz}

650.00

l

C0010 not effective in the case
of bipolar setpoint selection
(−10 V ... + 10 V)

l

C0010 only limits the analog
input 1

l

In the case of a max. output
frequency > 50 Hz the
switching threshold of the auto
DCB in C0019 has to be
increased.

l

From software 3.5: If
C0010 > C0011, the drive does
not start when controller
enable is set.

à

Speed setting range 1 : 6 for
Lenze geared motors: For
operation with Lenze geared
motors has to be set
necessarily.

^ 281

C0011

uSEr

Maximum
output
frequency

50.00 7.50

à

87 Hz

{0.02

Hz}

650.00

C0012

uSEr

Acceleration
time main
setpoint

5.00

0.00

{0.02 s}

1300.00 Reference: frequency change 0 Hz

... C0011

l

Additional setpoint

ðC0220

l

Acceleration times that can be
activated via digital signals

ð

C0101

^ 286

C0013

uSEr

Deceleration
time main
setpoint

5.00

0.00

{0.02 s}

1300.00 Reference: frequency change

C0011... 0 Hz

l

Additional setpoint

ðC0221

l

Deceleration times that can be
activated via digital signals

ð

C0103

^ 286

C0014

v

Operating
mode

2

2

V/f characteristic control V ~ f
(linear characteristic with constant
V

min

boost)

l

Commissioning is possible
without identifying motor
parameters

l

Advantage of identification
with C0148:
– Improved smooth running at

low speeds

– V/f rated frequency (C0015)

and slip (C0021) are
calculated and saved. They
do not have to be entered

^ 255

3

V/f characteristic control V ~ f

2

(square−law characteristic with
constant V

min

boost)

4

Vector control

In the case of the first selection
enter the motor data and identify
them with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be
set = 0 (automatic DC injection
brake is deactivated)

5

Sensorless torque control with speed
limitation

l

Torque setpoint via C0412/6

l

Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)

C0015

uSEr

V/f rated
frequency

50.00 7.50

{0.02

Hz}

960.00

l

C0015 is calculated and saved
during the motor parameter
identification with C0148.

l

The setting applies to all
permitted mains voltages

^ 257

^ 261

C0016

uSEr

V

min

boost

а

0.00

{0.01 %}

40.00

а

device−dependent

Setting applies to all permitted
mains voltages

^ 257