Function library
Code table
l
386
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0010
uSEr
Minimum
output
frequency
0.00
0.00
à
14.5 Hz
{0.02
Hz}
650.00
l
C0010 not effective in the case
of bipolar setpoint selection
(−10 V ... + 10 V)
l
C0010 only limits the analog
input 1
l
In the case of a max. output
frequency > 50 Hz the
switching threshold of the auto
DCB in C0019 has to be
increased.
l
From software 3.5: If
C0010 > C0011, the drive does
not start when controller
enable is set.
à
Speed setting range 1 : 6 for
Lenze geared motors: For
operation with Lenze geared
motors has to be set
necessarily.
^ 281
C0011
uSEr
Maximum
output
frequency
50.00 7.50
à
87 Hz
{0.02
Hz}
650.00
C0012
uSEr
Acceleration
time main
setpoint
5.00
0.00
{0.02 s}
1300.00 Reference: frequency change 0 Hz
... C0011
l
Additional setpoint
ðC0220
l
Acceleration times that can be
activated via digital signals
ð
C0101
^ 286
C0013
uSEr
Deceleration
time main
setpoint
5.00
0.00
{0.02 s}
1300.00 Reference: frequency change
C0011... 0 Hz
l
Additional setpoint
ðC0221
l
Deceleration times that can be
activated via digital signals
ð
C0103
^ 286
C0014
v
Operating
mode
2
2
V/f characteristic control V ~ f
(linear characteristic with constant
V
min
boost)
l
Commissioning is possible
without identifying motor
parameters
l
Advantage of identification
with C0148:
– Improved smooth running at
low speeds
– V/f rated frequency (C0015)
and slip (C0021) are
calculated and saved. They
do not have to be entered
^ 255
3
V/f characteristic control V ~ f
2
(square−law characteristic with
constant V
min
boost)
4
Vector control
In the case of the first selection
enter the motor data and identify
them with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be
set = 0 (automatic DC injection
brake is deactivated)
5
Sensorless torque control with speed
limitation
l
Torque setpoint via C0412/6
l
Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)
C0015
uSEr
V/f rated
frequency
50.00 7.50
{0.02
Hz}
960.00
l
C0015 is calculated and saved
during the motor parameter
identification with C0148.
l
The setting applies to all
permitted mains voltages
^ 257
^ 261
C0016
uSEr
V
min
boost
а
0.00
{0.01 %}
40.00
а
device−dependent
Setting applies to all permitted
mains voltages
^ 257