Function library, Code table – Lenze E82xVxxxKxxxxx User Manual
Page 401
Function library
Code table
l
401
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0190
*
v
(A)
Linking of main
and additional
setpoint
(PCTRL1−
ARITH1)
1
0
X + 0
Mathematical combination of
main setpoint (NSET1−NOUT) and
additonal setpoint (PCTRL1−NADD)
The result is provided in Hz
X = NSET1−NOUT
Y = PCTRL1−NADD
1
X + Y
2
X − Y
3
X @ Y
C0011
4
X
Y @
C0011
100
5
X @ C0011
C0011 * Y
C0191
(A)
Acceleration
time −
follow−up
controller
5.00
0.00
{0.02 s}
1300.00 Based on change 0 Hz ... C0011
C0192
(A)
Deceleration
time −
follow−up
controller
5.00
0.00
{0.02 s}
1300.00 Based on change C0011 ... 0 Hz
C0193
(A)
Follow−up
controller −
reset
5.00
0.00
{0.02 s}
1300.00 Based on change C0011 ... 0 Hz
Set the follow−up controller to "0"
C0194
(A)
Lower
threshold for
follow−up
controller
activation
−200.0
0
−200.00
{0.01 %}
200.00 Based on C0011
If the value falls below C0194:
Follow−up controller operates with
C0191 or C0192 towards −C0011
C0195
(A)
Upper
threshold for
follow−up
controller
activation
200.0
0
−200.00
{0.01 %}
200.00 Based on C0011
If C0195 is exceeded:
Follow−up controller operates with
C0191 or C0192 towards +C0011
C0196
*
v
Activation auto
DCB
0
0
Auto DCB active if PCTRL1−SET3 <
C0019
^ 292
1
Auto DCB active if PCTRL1−SET3 <
C0019 and NSET1−RFG1−IN < C0019
C0200
*
Software ID
Read only on PC
x = main version, y = subversion
82S8212V_xy000
8200 vector 0.25 ... 11 kW
82S8212V_xy010
8200 vector 15 ... 90 kW
C0201
*
Software
creation date
Read only on PC
C0202
*
Software ID
Output in keypad as string in four parts at four
characters each
Read only in keypad
1
82S8
2
212 V
3
_xy0
x = main version, y = subversion
4
zz
00 = 8200 vector 0.25 ... 11 kW
10 = 8200 vector 15 ... 90 kW
C0220
*
Acceleration
time −
additional
setpoint
(PCTRL1−NADD)
5.00
0.00
{0.02 s}
1300.00 Main setpoint
ð C0012
^ 286
C0221
*
Deceleration
time −
additional
setpoint
(PCTRL1−NADD)
5.00
0.00
{0.02 s}
1300.00 Main setpoint
ð C0013