5 ac motor braking, Ac motor braking, Function library – Lenze E82xVxxxKxxxxx User Manual

Page 294

Advertising
background image

Function library

Acceleration, deceleration, braking, stopping
AC motor braking

10

l

294

EDS82EV903 EN 3.0

10.6.5

AC motor braking

Description

With the parameter set changeover in dependence of the DC−bus voltage, the AC motor
braking can be used as alternative for DC braking (DCB). The AC motor braking is a braking
method without external brake resistor for the control mode V/f characteristic control
with linear characteristic".

)

Note!

The AC motor braking can only be used with the control mode V/f
characteristic control with linear characteristic" (C0014 = 2).

ƒ

With mains voltages up to approx. AC 400 V shorter braking times can be reached
than with the DC injection braking.

ƒ

The braking times for braking via an external brake resistor are approx. 33 % shorter
than for AC motor braking.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0988
*

DC−bus voltage
threshold for
DC−bus voltage
control

0

0
= changeover of
the parameter set
via DC−bus
voltage
deactivated

{1 %}

200

l

It is always changed over
between PAR1 and PAR2

l

Changeover of the parameter
set via terminal, bus or PC is
not possible if C988 > 0!

^ 278