Commissioning – Lenze E82xVxxxKxxxxx User Manual
Page 207
![background image](/manuals/566070/207/background.png)
Commissioning
Parameter setting with E82ZBC keypad
Vector control
l
207
EDS82EV903 EN 3.0
Comment
Switch−on sequence
12.
Activate the operating mode "vector control"
(C0014 = 4)
Lenze setting: Linear V/f characteristic control
(C0014 = 2)
E82ZBC014
z
y
w x
v
t
u
s
4
00 14
000
1
c
d
f
PS
p
Para
H/L
Subcode
Disp
Set
13.
Adapt the voltage/current range for the analog
setpoint selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
z
y
w x
0
000
a
b
c
d
e
m n o
p
q r
Hi
Lo
1
j g f k i h PS
0034
Set the DIP switch on the standard
I/O to the same range (see Mounting
Instructions for the standard I/O)
14.
Enter the motor data
See motor nameplate
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depending on the controller
Enter the value for the motor circuit
configuration (star/delta) selected!
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depending on the controller
Enter the value for the motor circuit
configuration (star/delta) selected!
E
Motor cos
j (C0091)
Lenze setting: Depending on the controller
15.
Start the motor parameter identification (C0148)
Only when the motor is cold!
A
Ensure that the controller is inhibited
misc001
20
28
X3
}
Terminal X3/28 = LOW
B
Set C0148 = 1
Press
v
C
Enable the controller
misc002
20
28
X3
l
Terminal X3/28 = HIGH
l
The identification starts:
– Segment
c is off
– The motor consumes current
and makes a high−pitched"
tone.
– The motor does not rotate!
D
If segment
c becomes active again after
approx. 30 s, inhibit controller again.
misc001
20
28
X3
}
l
Terminal X3/28 = LOW
l
Identification is completed.
l
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance
(C0092)
l
Measured and stored:
– Motor stator resistance (C0084)
= Total resistance of motor
cable and motor
16.
If necessary, select more parameters
Activate e.g. JOG
frequencies (C0037,
C0038, C0039) or motor
temperature monitoring
(C0119)
When all settings are complete:
17.
Select setpoint
E.g. via potentiometer at
terminals 7, 8, 9
18.
Enable the controller
20
28
X3
misc002
Terminal X3/28 = HIGH
19.
The drive is now running.
If the drive does not start,
additionally press
u