Commissioning – Lenze E82xVxxxKxxxxx User Manual

Page 207

Advertising
background image

Commissioning

Parameter setting with E82ZBC keypad

Vector control

8

l

207

EDS82EV903 EN 3.0

Comment

Switch−on sequence

12.

Activate the operating mode "vector control"
(C0014 = 4)
Lenze setting: Linear V/f characteristic control
(C0014 = 2)

E82ZBC014

z
y

w x

v

t

u

s

4

00 14

000

1

c

d

f

PS

Œ

p

Para

H/L

Subcode

Disp

Set

13.

Adapt the voltage/current range for the analog
setpoint selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)

z
y

w x

0

000

a

b

c

d

e

‚m n o

p

q r

Hi
Lo

1

j g f k i h PS

Œ

0034

Set the DIP switch on the standard
I/O to the same range (see Mounting
Instructions for the standard I/O)

14.

Enter the motor data

See motor nameplate

A

Rated motor speed (C0087)
Lenze setting: 1390 rpm

B

Rated motor current (C0088)
Lenze setting: Depending on the controller

Enter the value for the motor circuit
configuration (star/delta) selected!

C

Rated motor frequency (C0089)
Lenze setting: 50 Hz

D

Rated motor voltage (C0090)
Lenze setting: Depending on the controller

Enter the value for the motor circuit
configuration (star/delta) selected!

E

Motor cos

j (C0091)

Lenze setting: Depending on the controller

15.

Start the motor parameter identification (C0148)

Only when the motor is cold!

A

Ensure that the controller is inhibited

misc001

20

28

X3

}

Terminal X3/28 = LOW

B

Set C0148 = 1

Press

v

C

Enable the controller

misc002

20

28

X3

l

Terminal X3/28 = HIGH

l

The identification starts:
– Segment

c is off

– The motor consumes current

and makes a high−pitched"
tone.

– The motor does not rotate!

D

If segment

c becomes active again after

approx. 30 s, inhibit controller again.

misc001

20

28

X3

}

l

Terminal X3/28 = LOW

l

Identification is completed.

l

Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance

(C0092)

l

Measured and stored:
– Motor stator resistance (C0084)

= Total resistance of motor
cable and motor

16.

If necessary, select more parameters

Activate e.g. JOG
frequencies (C0037,
C0038, C0039) or motor
temperature monitoring
(C0119)

When all settings are complete:

17.

Select setpoint

E.g. via potentiometer at
terminals 7, 8, 9

18.

Enable the controller

20

28

X3

misc002

Terminal X3/28 = HIGH

19.

The drive is now running.

If the drive does not start,
additionally press

u