Function library – Lenze E82xVxxxKxxxxx User Manual
Page 433
![background image](/manuals/566070/433/background.png)
Function library
Code table
l
433
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0599
*
v
Current limit
value − motor
phase failure
detection
5
1
{1 %}
50
l
Operating threshold for C0597
l
Reference: rated controller
current
C0608
*
Fan monitoring
0
0
Inactive
8200 motec 3 ... 7.5 kW:
Function must be activated during
commissioning (recommended:
C0608 = 1)! Otherwise, the
controller may be destroyed due
to overheating.
For all other controllers:
It is essential to set C0608 = 0.
1
TRIP error message
2
Warning
C0625
*
Blocking
frequency 1
0.00
0.00
{0.02
Hz}
650.00
^ 273
C0626
*
Blocking
frequency 2
0.00
0.00
{0.02
Hz}
650.00
C0627
*
Blocking
frequency 3
0.00
0.00
{0.02
Hz}
650.00
C0628
*
Skipping
bandwidth −
blocking
frequencies
0.00
0.00
{0.01 %}
100.00 Applies to C0625, C0626, C0627
C0988
*
DC−bus voltage
threshold for
DC−bus voltage
control
0
0
= changeover of
the parameter set
via DC−bus
voltage
deactivated
{1 %}
200
l
It is always changed over
between PAR1 and PAR2
l
Changeover of the parameter
set via terminal, bus or PC is
not possible if C988 > 0!
^ 278
^ 294
C1500
*
(A)
Software ID
application I/O
82SAFA0B_xy000
Read only on PC
x = main version
y = subversion
C1501
*
(A)
Software
creation date −
application I/O
Read only on PC
C1502
*
(A)
Software ID
application I/O
Output in keypad as string in four parts at four
characters each
Read only in keypad
x = main version
y = subversion
1
82SA
2
FA0B
3
_xy0
4
00
C1504
(A)
Service codes −
application I/O
Alterations by Lenze service only!
...
C1507
(A)
C1550
(A)
Service code −
application I/O
Alterations by Lenze service only!