4 resetting fault messages, Troubleshooting and fault elimination – Lenze E82xVxxxKxxxxx User Manual

Page 459

Advertising
background image

Troubleshooting and fault elimination

Resetting fault messages

11

l

459

EDS82EV903 EN 3.0

11.4

Resetting fault messages

Eliminating the cause for TRIP error message

After eliminating the cause for a TRIP error message the error message must be reset with
the "TRIP reset" order. Only then the drive will start again.

)

Note!

A TRIP error message can have several causes. The TRIP reset can only be
carried out after all causes for the TRIP have been eliminated.

Manual or automatic TRIP reset

You can select whether errors occurred are to be reset manually or automatically. Mains
disconnection always carries out a TRIP reset independent of the settings under C0170.

)

Note!

If the controller carries out more than eight automatic TRIP resets within ten
minutes, the controller will set TRIP rST (Counter exceeded).
TRIP reset also resets the auto TRIP counter.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0043
*

v

TRIP reset

0

No current fault

Reset active fault with C0043 = 0

1

Fault active

C0170

v

Configuration
of TRIP reset

0

0

TRIP reset by mains switching,

s,

LOW edge at X3/28, via function
module or communication module

l

TRIP reset via function module
or communication module
with C0043, C0410/12 or
C0135 bit 11

l

Auto TRIP reset automatically
resets all faults after the time
in C0171 has elapsed

^ 459

1

Like 0 and additionally auto TRIP reset

2

TRIP reset by mains switching, via
function module or communication
module

3

TRIP reset by mains switching

C0171 Delay for auto

TRIP reset

0.00

0.00

{0.01 s}

60.00