Function library – Lenze E82xVxxxKxxxxx User Manual
Page 290
![background image](/manuals/566070/290/background.png)
Function library
Acceleration, deceleration, braking, stopping
Quick stop
l
290
EDS82EV903 EN 3.0
Activation
Via digital signal:
Link C0410/4 to a digital signal source.
ƒ
LOW level at signal source activates quick stop
ƒ
Level inversion possible with C0411
)
Note!
Quick stop can also be activated if the "Fail−safe changeover of the direction of
rotation" function is used. (
¶ 291)
In addition to the free configuration in C0410 you can also use the fixed
assignment in C0007 to link the function with a digital input.
Via keyboard of the keypad:
For this purpose, assign the quick stop function to the key:
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0469
*
s
Function of the
s key of the
keypad
1
0
Stop key without function
Determines the function to be
executed when the stop key is
pressed
l
s activates quick stop
l
U restarts the drive
Changes are only active after
mains connection!
1
CINH (controller inhibit)
2
QSP (quick stop)