Function library – Lenze E82xVxxxKxxxxx User Manual
Page 324
Function library
Process controller
Select the actual value source for the process controller
l
324
EDS82EV903 EN 3.0
10.9.3
Select the actual value source for the process controller
Description
The actual value is the process feedback signal (e.g. from a pressure encoder or a speed
encoder).
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0051
*
Output
frequency with
slip
compensation
(MCTRL1−NOUT
+SLIP) or
Actual process
controller
value
(PCTRL1−ACT)
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
During operation without process
controller (C0238 = 2):
l
Read only: output frequency
with slip compensation
(MCTRL1−NOUT+SLIP)
During operation with process
controller (C0238 = 0, 1):
l
Selection if C0412/5 =
FIXED−FREE (not assigned)
l
Display if C0412/5 is linked to
a signal source
^ 324
Activation
The actual process controller value (PCTRL1−ACT) must be linked with an analog input
signal under C0412/5.
Use C0051 to display the current actual process controller value.
)
Note!
If you do not link an analog input signal with the actual process controller
value under C0412/5, the actual process controller value can be directly
selected under C0051.