Function library – Lenze E82xVxxxKxxxxx User Manual

Page 324

Advertising
background image

Function library

Process controller
Select the actual value source for the process controller

10

l

324

EDS82EV903 EN 3.0

10.9.3

Select the actual value source for the process controller

Description

The actual value is the process feedback signal (e.g. from a pressure encoder or a speed
encoder).

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0051
*

Output
frequency with
slip
compensation
(MCTRL1−NOUT
+SLIP) or
Actual process
controller
value
(PCTRL1−ACT)

−650.00

{0.02

Hz}

650.00 The set value will be lost during

mains switching!
During operation without process
controller (C0238 = 2):

l

Read only: output frequency
with slip compensation
(MCTRL1−NOUT+SLIP)

During operation with process
controller (C0238 = 0, 1):

l

Selection if C0412/5 =
FIXED−FREE (not assigned)

l

Display if C0412/5 is linked to
a signal source

^ 324

Activation

The actual process controller value (PCTRL1−ACT) must be linked with an analog input
signal under C0412/5.

Use C0051 to display the current actual process controller value.

)

Note!

If you do not link an analog input signal with the actual process controller
value under C0412/5, the actual process controller value can be directly
selected under C0051.

Advertising