Function library
Code table
l
407
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0311
*
v
Functions for
special
applications 2
1
0
All functions switched off
A combination of functions can be
activated by entering the sum of
the selection values.
(C0156 from
software
version 3.1,
C0056 from
software
version 3.5)
1
Selection:
l
Reference variable for current
threshold C0156
l
Display value in C0056
Function active:
Function switched−off:
In the "V/f characteristic control"
operating mode
In the "V/f characteristic control"
operating mode:
l
C0156: rated controller current
l
C0156: rated controller current
l
C0056: device utilisation
(MCTRL−MOUT)
l
C0056: device utilisation
(MCTRL−MOUT)
In the "Vector control" or "Sensorless
torque control" operating mode:
In the "Vector control" or
"Sensorless torque control"
operating mode: rated motor
torque
l
C0156: rated controller current
l
C0156: rated motor torque
l
C0056: device utilisation
(MCTRL−MOUT)
l
C0056: actual torque value
(MCTRL-MACT)
(from software
version 3.1)
2
Influence of the S−ramp
Function active:
Function switched−off:
The S−ramp (C0182) does not affect the
quick stop ramp (C0105).
The S−ramp (C0182) also affects
quick stop.
(from software
version 3.5)
4
Selection of the flying restart
function
Function active:
Function switched−off:
Optimised flying restart function
active for two−pole motors
Standard flying restart function
active
(from software
version 3.7)
8
Delayed parameter set
changeover during operation
Function active:
Function switched−off:
Changeover between parameter sets
(as in software version 3.1) active
without delay
The first changeover between
parameter sets is carried out
without delay, any following
changeover will have a delay of 20
ms
16
Switch−on behaviour of the brake
transistor, depending on device
status TRIP
Function active:
Function switched−off:
The brake transistor is switched on if
the DC−bus voltage exceeds the brake
transistor threshold (C0174). It stays
switched off permanently if the TRIP
device status is active.
The brake transistor is also
switched on in the TRIP device
status if the DC−bus voltage
exceeds the brake transistor
threshold (C0174).
C0320
(A)
Actual process
controller value
(PCTRL1−ACT)
−650.00
{0.02
Hz}
650.00 Read only
C0321
(A)
Process
controller
setpoint
(PCTRL1−SET)
−650.00
{0.02
Hz}
650.00 Read only
C0322
(A)
Process
controller
output without
feedforward
control
(PCTRL1−OUT)
−650.00
{0.02
Hz}
650.00 Read only