Function library – Lenze E82xVxxxKxxxxx User Manual

Page 259

Advertising
background image

Function library

Operating mode

V/f characteristic control

10

l

259

EDS82EV903 EN 3.0

Typical values for C0015

400 V controller E82xVxxxK4C

230 V controller E82xVxxxK2C

Motor

C0015

Motor

C0015

Voltage

Frequency

Connection

Voltage

Frequency

Connection

230/400 V

50 Hz

*

50 Hz

230/400 V

50 Hz

F

50 Hz

220/380 V

50 Hz

*

52.6 Hz

220/380 V

50 Hz

F

52.3 Hz

280/480 V

60 Hz

*

50 Hz

400/690 V

400 V

50 Hz
50 Hz

F

50 Hz

230/400 V
280/480 V

400 V

50 Hz
60 Hz
87 Hz

F

87 Hz

220/380 V

50 Hz

F

90.9 Hz

)

Note!

ƒ

4−pole asynchronous motors which are designed for a rated frequency of
50 Hz in star connection can be operated in delta connection up to 87 Hz
when being constantly excited.
– The motor current and the motor power are then increased by the factor

Ö3 = 1.73.

– The field−weakening range starts above 87 Hz.

ƒ

Advantages:
– Higher speed−setting range
– 73 % higher power efficiency with standard motors.

ƒ

Basically, this procedure can also be used for motors with other numbers of
poles.
– Observe mechanical limit speeds in case of two−pole asynchronous

motors.

Advertising