Application examples

Pressure control
Example 2: Simple pressure control with changeable setpoint selection

15

l

506

EDS82EV903 EN 3.0

Application−specific configuration

Code

Settings

IMPORTANT

No.

Name

Value

Meaning

C0014 Operating mode

3

V/f characteristic control V

~f

2

square−law characteristic with
constant V

min

boost

C0019 Operating

threshold −
automatic DC
injection brake
(auto DCB)

0

Automatic DC injection brake is deactivated

If the lower frequency limitation is
activated (C0239) or if C0181 is used
as controller setpoint (C0145), the
automatic DC injection brake must
be deactivated!

C0106 Hold time −

automatic DC
injection brake
(auto DCB)

0

Automatic DC injection brake is deactivated

C0070 Process

controller gain

1.00

Lenze default
setting

Adapt to process, if required.

à

Further information:

^ 318 ff.

C0071 Process

controller reset
time

100

Lenze default
setting

C0074 Influence of the

process
controller

100.0

0.0

{0.1 %}

100.0

C0145 Source of

process
controller
setpoint

0

Overall setpoint (PCTRL1−SET3)

Setpoint = NSET1−NOUT +
PCTRL1−NADD
(Main setpoint + additional setpoint)

C0181 Process

controller
setpoint 2
(PCTRL1−SET2)

−650.00

{0.02

Hz}

650.0

C0238 Frequency

precontrol

0

No feedforward control (only process controller)

Process controller has full influence.

C0239 Lower frequency

limitation

³ 0

Prevent reversed rotation

The value does not fall below the
limit independently of the setpoint.
Automatic DC injection brake (auto
DCB) must be deactivated with
C0019 = 0 or C0106 = 0

C0412

Linking analog signal sources to internal analog
signals

1 Setpoint 1

(NSET1-N1)

255

fixed free (disconnect from analog input)

The analog input of the standard I/O
(AIN1) is linked factory−set to the
speed feedforward control. This
connection must be separated so
that the input can be used for the
analog actual value (C0412/5).

2 Setpoint 2

(NSET1-N2)

255

5 Actual process

controller value
(PCTRL1−ACT)

1

Analog input X3/8 of the standard I/O

Actual pressure value

)

Note!

ƒ

The motor potentiometer in connection with the standard I/O may only be
linked with the signals NSET1−N1, NSET1−N2 or PCTRL1−NADD. The linkage
with other signals would cause a setpoint step−change.

ƒ

When selecting the setpoint via the motor potentiometer, we recommend
the acceleration and deceleration times

³ 5s (C0220, C0221).