Safety instructions – Lenze E82xVxxxKxxxxx User Manual

Page 25

Advertising
background image

Safety instructions

Safety instructions for the installation according to U

L

or U

R

3

l

25

EDS82EV903 EN 3.0

3.3

Safety instructions for the installation according to U

L

or U

R

J

Warnings!

ƒ

Motor Overload Protection
– For information on the protection level of the internal overload protection

for a motor load, see the corresponding manuals or software helps.

– If the integral solid state motor overload protection is not used, external or

remote overload protection must be provided.

ƒ

Branch Circuit Protection
– The integral solid state protection does not provide branch circuit

protection.

– Branch circuit protection has to be provided externally in accordance with

corresponding instructions, the National Electrical Code and any
additional codes.

ƒ

Please observe the specifications for fuses and screw−tightening torques in
these instructions.

ƒ

E82xV251K2C ... E82xV222K2C (0.25 kW ... 2.2 kW, 240 V devices):
– Suitable for use on a circuit capable of delivering not more than 5000 rms

symmetrical amperes, 240 V maximum, when protected by fuses or circuit
breakers.

– Suitable for use on a circuit capable of delivering not more than 50000 rms

symmetrical amperes, 240 V maximum, when protected by CC, J, T or R
class fuses.

– Shall be installed in a Pollution Degree 2 macro−environment.
– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.

ƒ

E82xV551K4C ... E82xV222K4C (0.55 kW ... 2.2 kW, 400/500 V devices):
– Suitable for use on a circuit capable of delivering not more than 5000 rms

symmetrical amperes, 500 V maximum, when protected by fuses or circuit
breakers.

– Suitable for use on a circuit capable of delivering not more than 50000 rms

symmetrical amperes, 500 V maximum, when protected by CC, J, T or R
class fuses.

– Shall be installed in a Pollution Degree 2 macro−environment.
– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.