Setpoints via fixed setpoints (JOG)

Description

You can store up to three fixed setpoints per parameter set and retrieve them using digital
input signals.

At operation with application I/O 7 fixed setpoints are available per parameter set.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0037 JOG1

20.00 −650.00

{0.02

Hz}

650.00 JOG = fixed setpoint

Additional fixed setpoints

ðC0440

^ 309

C0038 JOG2

30.00 −650.00

{0.02

Hz}

650.00

C0039 JOG3

40.00 −650.00

{0.02

Hz}

650.00

C0440
(A)

Additional JOG
values

−650.00

{0.02

Hz}

650.00 JOG = fixed setpoint

Activation via configuration in
C0410

^ 309

1 JOG 1

20.00

C04401/1 and C0037 are the
same

2 JOG 2

30.00

C04401/2 and C0038 are the
same

3 JOG 3

40.00

C04401/3 and C0039 are the
same

4 JOG 4

15.00

5 JOG 5

25.00

6 JOG 6

35.00

7 JOG 7

45.00

Activation

Operation without application I/O

ƒ

In C0410/1, link the NSET1−JOG1/3 signal to a digital input signal.

ƒ

In C0410/2, link the NSET1−JOG2/3 signal to a digital input signal.