2 parameter set changeover, Function library – Lenze E82xVxxxKxxxxx User Manual

Page 372

Advertising
background image

Function library

Parameter set management
Parameter set changeover

10

l

372

EDS82EV903 EN 3.0

10.16.2

Parameter set changeover

Description

During operation you can change between the four parameter sets of the controller via
digital signals. Thus 9 additional JOG values or additional acceleration and deceleration
times are available.

The parameter set changeover via digital signals is not possible if the automatic
changeover via DC−bus voltage is active!

Activation

Link C0410/13 (DCTRL1−PAR2/4) and C0410/14 (DCTRL1−PAR3/4) to a digital signal source.

After initialisation, the controller always operates with parameter set 1. The controller will
not perform a parameter set changeover before a parameter set changeover signal is
active.

)

Note!

ƒ

C0410/13 and C0410/14 must be linked to the same signals in all parameter
sets!

ƒ

Start the parameterisation with the highest parameter set. Carry out
parameterisation for parameter set 1 last. That way, undefined statuses are
avoided.

ƒ

If different operating modes (C0014) are set in the parameter sets, the
parameter sets should only be changed over when the controller is inhibited
(CINH).

Signal source

Active parameter set

Level at C0410/13

Level at C0410/14

LOW

LOW

Parameter set 1 (PAR1)

HIGH

LOW

Parameter set 2 (PAR2)

LOW

HIGH

Parameter set 3 (PAR3)

HIGH

HIGH

Parameter set 4 (PAR4)

)

Note!

In C0007, the changeover between parameter set 1 and parameter set 2 can be
linked to digital inputs X3/E2 or X3/E3.