Function library – Lenze E82xVxxxKxxxxx User Manual

Page 380

Advertising
background image

Function library

Code table

10

l

380

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0002
*

s

uSEr

Parameter set
management

0

0

Ready

PAR1 ... PAR4:

l

Parameter sets of the
controller

l

PAR1 ... PAR4 also contain the
parameters for the function
modules standard I/O,
application I/O, AS interface,
system bus (CAN)

FPAR1:

l

Module−specific parameter set
of the fieldbus function
modules INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen

l

FPAR1 is saved in the function
module

^ 368

Restoring the
delivery status

1

Lenze setting

ð PAR1

Restore the delivery status in the
parameter set selected

2

Lenze setting

ð PAR2

3

Lenze setting

ð PAR3

4

Lenze setting

ð PAR4

31

Lenze setting

ð FPAR1

Restore the delivery status in the
fieldbus function module

61

Lenze setting

ð PAR1 + FPAR1

Restore the delivery status in the
selected parameter set of the
controller and in the fieldbus
function module

62

Lenze setting

ð PAR2 + FPAR1

63

Lenze setting

ð PAR3 + FPAR1

64

Lenze setting

ð PAR4 + FPAR1

C0002
*

s

uSEr

(Cont.)

Transferring
parameter sets
with the
keypad

By means of the keypad you can
transfer the parameter sets to
other controllers.
During the transmission the
access to the parameters via other
channels is inhibited!

Keypad

ð controller

Overwrite all available parameter
sets (PAR1 ... PAR4, if required
FPAR1) with the corresponding
data of the keypad

70

with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen

10

with all other function modules