Troubleshooting and fault elimination

Drive behaviour in the event of faults

11

l

454

EDS82EV903 EN 3.0

11.2

Drive behaviour in the event of faults

The controller responds differently to the three possible fault types (TRIP, message, or
warning):

TRIP (keypad display:

a)

ƒ

Switches the power outputs U, V, W to high resistance until TRIP is reset.

ƒ

The fault indication is entered into C0161 of the history buffer as "current fault".

ƒ

The drive coasts without control!

ƒ

After TRIP reset (

459):

– The drive accelerates to its setpoint along the set ramps.
– The fault indication is moved to C0162 as "last fault" and is deleted in C0161.

Messages (keypad display:

c)

ƒ

Switches the power outputs U, V, W to high resistance.

ƒ

Messages are not entered into the history buffer.

ƒ

The drive coasts without control as long as the message is active!

ƒ

If the message is no longer active, the drive starts automatically.

Warnings

"Heatsink overtemperature" (keypad:OH

e)

ƒ

The drive is operated in a controlled mode!

ƒ

The warning signal goes off if the fault is no longer active.

"Error in motor phase" (keypad:LP1)

"PTC monitoring" (keypad:OH51)

ƒ

The drive is operated in a controlled mode!

ƒ

The fault indication is entered into C0161 of the history buffer as "current fault".

ƒ

After TRIP reset the fault indication is moved to C0162 as "last fault" and is deleted
in C0161.