Electrical installation, Operation at rated power, Operation with increased rated power – Lenze E82xVxxxKxxxxx User Manual

Page 152

Advertising
background image

Electrical installation

Standard devices in the power range of 55 kW
Fuses and cable cross−sections according to EN 60204−1

6

l

152

EDS82EV903 EN 3.0

6.7.3

Fuses and cable cross−sections according to EN 60204−1

Supply conditions

Range

Description

Fuses

l

Utilisation category: only gG/gL or gRL

Cables

Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).

RCCB

l

Controllers can cause a DC current in the PE conductor. If a residual current device (RCD) or a
fault current monitoring unit (RCM) is used for protection in the case of direct or indirect
contact, only one RCD/RCM of the following type can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for connection to a

1−phase system

Alternatively another protective measure can be used, like for instance isolation from the
environment by means of double or reinforced insulation, or isolation from the supply system
by using a transformer.

l

Earth−leakage circuit breakers must only be installed between mains supply and controller.

Observe all national and regional regulations!

Operation at rated power

8200 vector

Rated fuse current

Cable cross−section

FI

1)

Fuse

Circuit−breaker

Laying system L1, L2, L3, PE

B2

C

Type

[A]

[A]

[mm

2

]

[mm

2

]

[mA]

Mains 3/PE AC 400/500 V − operation without mains choke/mains filter

E82xV453K4B

Operation only permitted with mains choke or mains filter

E82xV553K4B

Mains 3/PE AC 400/500 V − operation with mains choke/mains filter

E82xV453K4B

100

35

³ 300

E82xV553K4B

125

35

1)

Earth−leakage circuit breaker

Operation with increased rated power

8200 vector

Rated fuse current

Cable cross−section

FI

1)

Fuse

Circuit−breaker

Laying system L1, L2, L3, PE

B2

C

Type

[A]

[A]

[mm

2

]

[mm

2

]

[mA]

Mains 3/PE AC 400 V − operation without mains choke/mains filter

E82xV453K4B

Operation only permitted with mains choke or mains filter

E82xV553K4B

Mains 3/PE AC 400 V − operation with mains choke/mains filter

E82xV453K4B

125

35

³ 300

E82xV553K4B

160

70

1)

Earth−leakage circuit breaker