Acceleration, deceleration, braking, stopping
Setting of acceleration times, deceleration times and S−shaped ramps
l
287
EDS82EV903 EN 3.0
Adjustment
ƒ
The acceleration and deceleration times refer to an output frequency change from
0 Hz to the max. output frequency set in C0011.
ƒ
Calculate the times T
ir
and T
if
, which you can set under C0012 and C0013.
T
ir
+ t
ir
@ C0011
f
2
* f
1
t
ir
and t
if
are the desired times for the change between
f
1
and f
2.
T
if
+ t
if
@ C0011
f
2
* f
1
)
Note!
If the acceleration and deceleration times are set too short, and under
unfavourable operating conditions, the controller can be switched off with
TRIP OC5. In these cases, the acceleration and deceleration times must be set
so that the drive can follow the speed profile without Imax reaching a drive
system.
Set linear ramps
C0182 = 0.00: ramp function generator for the main setpoint operates linearly
f [ H z ]
f 2
C 0 0 1 1
f 1
0
t i r
t i f
T i r
T i f
t
8200vec527
Fig. 10−6
Acceleration times and deceleration times for linear ramp function generator