Commissioning – Lenze E82xVxxxKxxxxx User Manual
Page 221
![background image](/manuals/566070/221/background.png)
Commissioning
Important codes for quick commissioning
l
221
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0517
*
v
User menu
l
After mains switching or in the
g function the code from
C0517/1 is displayed.
l
In the Lenze setting the user
menu contains the most
important codes for
commissioning the operating
mode "V/f characteristic control
with a linear characteristic"
l
If the password protection is
active, only the codes entered
in C0517 can be freely accessed
l
If less than 10 codes are
required, assign the value "0"
(zero) to the memory locations
not used. Please observe that
the software automatically
assigns code C0050 to a
memory location that is not
used, if it has not been
explicitly assigned to another
memory location.
^ 373
1 Memory 1
50
C0050
Output frequency (MCTRL1−NOUT)
2 Memory 2
34
C0034
Range of analog setpoint selection
3 Memory 3
7
C0007
Fixed configuration of digital input
signals
4 Memory 4
10
C0010
Minimum output frequency
5 Memory 5
11
C0011
Maximum output frequency
6 Memory 6
12
C0012
Acceleration time main setpoint
7 Memory 7
13
C0013
Deceleration time main setpoint
8 Memory 8
15
C0015
V/f rated frequency
9 Memory 9
16
C0016
V
min
boost
10 Memory 10
2
C0002
Parameter set transfer
Possible entries for C0517
xxxx
All codes apart from the codes labelled
with "(A)".
Syntax:
Codes: C0517/x = cccc
Subcodes: C0517/x = cccc.ss