Function library, Code table – Lenze E82xVxxxKxxxxx User Manual

Page 388

Advertising
background image

Function library

Code table

10

l

388

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0034
*

v

uSEr

Range of
setpoint
selection
Standard I/O
(X3/8)

Observe switch position of the
function module!

^ 298

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA

1

Current 4 ... 20 mA

Reversal of rotation direction only
possible with a digital signal.

2

Bipolar voltage −10 V ... +10 V

l

Minimum output frequency
(C0010) not effective

l

Individually adjust offset and
gain

3

Current 4 ... 20 mA open−circuit
monitored

TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.

C0034
*

v

(A)

uSEr

Range of
setpoint
selection
Application I/O

Observe jumper position of the
function module!

^ 298

1 X3/1U, X3/1I

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V

2 X3/2U, X3/2I

1

Bipolar voltage −10 V ... +10 V

Minimum output frequency
(C0010) not effective

2

Current 0 ... 20 mA

3

Current 4 ... 20 mA

Reversal of rotation direction only
possible with a digital signal.

4

Current 4 ... 20 mA open−circuit
monitored

Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA

C0035
*

v

Operation
mode − DC
injection brake
(DCB)

0

0

Brake voltage selection under C0036

Hold time

ð C0107

^ 292

1

Brake current selection under C0036

C0036 Voltage/

current DC
injection brake
(DCB)

а

0.00

{0.01 %}

150.00 %

а

Device−dependent

l

Based on V

rated

, I

rated

l

Setting applies to all permitted
mains voltages

^ 292

C0037 JOG1

20.00 −650.00

{0.02

Hz}

650.00 JOG = fixed setpoint

Additional fixed setpoints

ðC0440

^ 309

C0038 JOG2

30.00 −650.00

{0.02

Hz}

650.00

C0039 JOG3

40.00 −650.00

{0.02

Hz}

650.00

C0040
*

v

Controller
inhibit (CINH)

−0−

Controller inhibited (CINH)

Controller can only be enabled if
X3/28 = HIGH

^ 277

−1−

Controller enabled (CINH)

C0043
*

v

TRIP reset

0

No current fault

Reset active fault with C0043 = 0

1

Fault active

C0044
*

Setpoint 2
(NSET1-N2)

−650.00

{0.02

Hz}

650.00 The set value will be lost during

mains switching!

l

Selection if C0412/2 =
FIXED−FREE (not assigned)

l

Display if C0412/2 is linked to
a signal source

^ 311

C0046
*

Setpoint 1
(NSET1-N1)

−650.00

{0.02

Hz}

650.00 The set value will be lost during

mains switching!

l

Selection if C0412/1 =
FIXED−FREE (not assigned)

l

Display if C0412/1 is linked to
a signal source

^ 311